In Circuits you create each board’s circuits without Revit’s own circuit tools and without setting up a main supply or breakers first. They stay normal Revit circuits, so schedules, tags and MagiCAD still work.
Add a board
Click Add board
Add board is beside the Floor choice on the Circuits page.
Click the sikringsskap in the view
A Revit board, or one Pembris already placed there, simply opens.
Name the board
Anything else, such as a Generic Model cabinet, gets a Pembris board at it. A small window names it after its Mark, else the next free U-number, never its type’s long name. The cabinet stays as it is. If you chose Use my Revit setup, it asks first, offering Pembris setup for that board.
Choose a circuit setup
The first time you click New circuit in a project, it asks how to treat Revit’s setup. Opening Circuits never asks. Cancel makes no circuit.
| Choice | What it does |
|---|---|
| Use my Revit setup (selected first) | Uses the boards and devices as you set them up in Revit. A board must be Electrical Equipment with a power connector and a distribution system; a device without a power connector is refused while picking. |
| Let Pembris fill in the setup | Adds what is missing: a Pembris board, a distribution system (Pembris 230 V, or Pembris 400/230 V for a 400 V board) and a Pembris connection at a device with no power connector. |
The choice holds for the project until Revit closes; tick Remember for this project to never be asked again. Circuit setup… under the gear asks again. Changing it never changes circuits already made.
Make a circuit
Open the board
New circuit is on a board’s page only, so the circuit lands on the board shown.
Click New circuit and type its name
The board shown is chosen first.
Click Create circuit (Enter)
It makes one Revit power circuit, with your name as Revit’s Load Name, in one undo step. Revit numbers it. The board shows it under Needs a look, No devices yet.
Add its devices, now or later
On the circuit’s page, Add devices… (Add or remove devices… once it has some) picks in the view. Each click adds a device, a second click takes it off, and Esc finishes. A click that can’t join says why in the bar at the bottom of the view.
A device already on another circuit Pembris made moves to this one, and the bar says so. A device on a circuit Pembris didn’t make stays there.
Rename and remove
- A circuit New circuit made has Rename… and Remove…. Remove asks first and leaves the devices where they are, on no circuit. A circuit made with Revit’s tools has neither.
- Rename board… and Remove board… are only on Pembris’s boards. Rename a Revit board in its Properties.
- Remove board… goes at once on a board with no circuits. With circuits it asks first, naming them, and removes them too; their devices stay where they are, on no circuit.
- Removing a circuit is refused, changing nothing, while a wire or tag of yours would go with it.
- Removing a board is refused, changing nothing, while a circuit made with Revit’s tools is on it or feeds it, or while something of yours, such as a tag or a panel schedule, depends on it. Removing a circuit leaves its board.