Every board needs a kursfortegnelse: the circuit list on the board door and in the handover papers, with each circuit’s longest cable length. Instead of writing circuit numbers on the plan with Revit’s text tool and measuring cables by hand, drops included, Circuits does it in one place: go to a board, see its circuits with one number each, mark them on the drawing and export the list.

See each circuit’s longest cable length and write labels on the plan.

Open Circuits

  1. Open the Pembris Electrical side pane

    Circuits lives in the side pane, not on the ribbon.

  2. Choose Circuits

    Click the Circuits row on Home (“Boards, cable lengths and labels”), or pick Circuits in the tool switcher at the top of the pane.

  3. Pick a board

    The list shows the project’s boards. Click one to see its circuits.

The board list

  • It lists every board with power circuits. Before there are any, it lists Pembris’s boards and Revit’s panelboards and switchboards that take power circuits.
  • Boards with a circuit that has no devices, or that fails a MagiCAD check, come first under Needs a look.
  • Each row says its level, so boards with the same name, such as one per flat, are told apart. A board without circuits says No circuits yet.
  • Floor shows one floor’s boards; All floors is the whole project. Add board sits beside it.
  • Export all N boards… exports every board the list shows. Tick boards to get Labels N and Export N… for just those.

A board’s page

The page shows the board’s name, level, circuit count and longest length, then New circuit, then its circuits, Needs a look first. Each circuit shows its longest cable length from the board, rounded up. Places kept free before the first circuit show as one Kept free row (for example “1–3”), spares as Reserve. Previous and next step through the boards.

You seeIt means
A length, such as 24 mMeasured along the drawn conduit and tray, rounded up.
~ before the lengthPart of it is planned, calculated or estimated, such as a drop that isn’t drawn.
?The length couldn’t be worked out: a device can’t be located, or the circuit has over 1,000 devices.
–The circuit has no devices yet.

The footer has Labels, Export… for this board and More: Copy list as text, Numbering…, Rename board… and Remove board… (on a Pembris board only) and Preferences….

A circuit’s page

A circuit’s page gives its number and board over its name, then the longest length and the device at its end, every device in cable order with its length, notes where a length is planned or estimated, and the parts of the length under Details. Opening a circuit shows its devices in the view. Change number… is on every circuit’s page, Revit’s own circuits included.

When the model changes

After a change to the project, the page says so and offers Refresh, keeping the board you are on. After Undo or Redo it says so at once; otherwise at your next click in the pane or when you switch views. Switching to another project empties the page.

What Circuits works with

  • Circuits made with Revit’s own tools

    Supported
  • Circuits made with New circuit

    Normal Revit power circuits

    Supported
  • MagiCAD Electrical circuits

    Reads MagiCAD’s circuit numbers, voltage drop and Ik min where MagiCAD has calculated

    Supported
  • Circuits and conduit in linked models

    Never read

    Not supported