Each circuit’s longest cable length is the cable from the board to its furthest device, measured along the joined conduit and cable tray in the model, however far it runs. Where nothing is drawn, Circuits plans the stretch and marks the length with ~.

What Circuits reads

Circuits reads the conduit, cable tray and fittings around the board and around each device, then follows real joins wherever a joined run goes, such as a riser or a run along the building. It reads at most 5,000 elements around one board; over that, lengths are planned and the board says so. It never reads linked models.

How the cable is followed

  • Conduit to the board. Where conduit connects a device to the board, the cable follows it by the shortest way.
  • Conduit ending above a device. An open conduit end right above or below a device, within 150 mm of its box in plan and 4 m in height, drops to it. The drop counts as planned, so the length gets ~.
  • Conduit into a tray. An open conduit end within 400 mm of a straight tray’s centreline drops into the tray; the gap is estimated.
  • Trays carry the cable. A device with no conduit and a straight tray within 6 m across, in plan, takes its cable from the tray at the tray’s nearest point. The circuit says “planned along the cable tray”.
  • Everything else is planned. A device no conduit reaches, or conduit that doesn’t reach the board, joins the cable at an open end, a tray or one of the circuit’s devices, the cheapest stretch first. A planned stretch never starts in the middle of conduit.

Planned stretches: ceiling or wall

Via the ceiling (the default), a planned stretch goes up to the cable height above its own level, across along the building’s axes and down again, so a device in a loop counts its drop twice. A circuit over two floors rises between them. In the wall, it goes across at the devices’ heights. A drop drawn as conduit is measured, never added again.

What a length is made of

Every length starts with the board tail and adds the slack of each device it reaches. Under Details, a circuit’s length is split into measured, planned, drops and rises, supplied and estimated parts, which always add up. Conduit elbows and couplings count their verified length; other fittings, and junction boxes between pieces, are measured through their centre as estimated.

Change the preferences

Preferences… (under the gear, or the board’s More) opens circuit-preferences.json in %LocalAppData%\Pembris Electrical. The file is yours, on this PC. It is written with the defaults the first time, and changes apply from the next measure. A missing or damaged value keeps its default.

`route`
`Ceiling` (default) or `Wall`
`cableHeightMm`
2400, above the board’s level
`boardTailMm`
1500
`slackPerDeviceMm`
300
`roundUpMm`
500
`trayReachMm`
6000; 0 follows trays only where drawn joins lead