Export… saves a circuit report for the boards you choose, in the format you pick in the Save dialog. Boards measured since the last change to the model are reused, though never across closing the project.

Export

  1. Choose the boards

    On a board’s page, Export… exports that board. In the board list, tick boards for Export N…, or use Export all N boards… for every board the list shows. Set Floor first to export one floor.

  2. Pick the format in the Save dialog

    Excel, CSV or PDF.

  3. Save

    The report is written where you chose.

Formats

  • Excel

    Exact lengths as numbers

    Supported
  • CSV

    UTF-8, semicolons with a decimal comma

    Supported
  • PDF kursfortegnelse

    A4 landscape, each board on its own pages with the project, board, level and date, the legend for “~” and page numbers

    Supported
  • Copy

    The same columns on the clipboard as tab-separated text

    Supported

Columns

The default columns follow the kursfortegnelse. Characteristic, RCD and reference method print blank, to fill in by hand, unless MagiCAD gives them. Unknown or unusable values are blank. In the Circuits preferences file you can change the columns and their order, the language (Norwegian or English) and decimalComma.

MagiCAD checks

Where MagiCAD Electrical has calculated a circuit (its Update writes the values), Circuits uses MagiCAD’s circuit number and fills the characteristic, RCD, reference method, rating and cable from MagiCAD where Revit has none. The report adds voltage drop (MagiCAD’s, cumulative from the main board, rounded up to 0.1%), Ik min (rounded down to whole amperes) and Check. MagiCAD’s values for a circuit it hasn’t calculated are treated as unknown.

What is checked

  • Voltage drop over the limit

    4% by default (`maxVoltageDropPercent`)

    Supported
  • Ik min too low to trip at once

    For B, C and D breakers: 5, 10 or 20 × the rating

    Supported
  • Cable longer than MagiCAD calculated with

    By more than 10% or 1 m, whichever is more: recalculate in MagiCAD

    Supported
  • Cable longer than MagiCAD’s longest allowed cable

    Supported
  • Fuses and other breaker curves

    Not checked

    Not supported

A circuit that fails a check says so on its board’s list and its page, with MagiCAD’s figures beside what they are checked against.

Save to
Any folder, OneDrive and DFS included; a symbolic link or junction in the path is refused
Formula-like text
Gets an apostrophe in front, in both CSV and Copy
Text too long for a cell
Replaced or cut, never stopping the export