Export… saves a circuit report for the boards you choose, in the format you pick in the Save dialog. Boards measured since the last change to the model are reused, though never across closing the project.
Export
Choose the boards
On a board’s page, Export… exports that board. In the board list, tick boards for Export N…, or use Export all N boards… for every board the list shows. Set Floor first to export one floor.
Pick the format in the Save dialog
Excel, CSV or PDF.
Save
The report is written where you chose.
Formats
- Supported
Excel
Exact lengths as numbers
- Supported
CSV
UTF-8, semicolons with a decimal comma
- Supported
PDF kursfortegnelse
A4 landscape, each board on its own pages with the project, board, level and date, the legend for “~” and page numbers
- Supported
Copy
The same columns on the clipboard as tab-separated text
Columns
The default columns follow the kursfortegnelse. Characteristic, RCD and reference method print blank, to fill in by hand, unless MagiCAD gives them. Unknown or unusable values are blank. In the Circuits preferences file you can change the columns and their order, the language (Norwegian or English) and decimalComma.
MagiCAD checks
Where MagiCAD Electrical has calculated a circuit (its Update writes the values), Circuits uses MagiCAD’s circuit number and fills the characteristic, RCD, reference method, rating and cable from MagiCAD where Revit has none. The report adds voltage drop (MagiCAD’s, cumulative from the main board, rounded up to 0.1%), Ik min (rounded down to whole amperes) and Check. MagiCAD’s values for a circuit it hasn’t calculated are treated as unknown.
What is checked
- Supported
Voltage drop over the limit
4% by default (`maxVoltageDropPercent`)
- Supported
Ik min too low to trip at once
For B, C and D breakers: 5, 10 or 20 × the rating
- Supported
Cable longer than MagiCAD calculated with
By more than 10% or 1 m, whichever is more: recalculate in MagiCAD
- Supported
Cable longer than MagiCAD’s longest allowed cable
- Not supported
Fuses and other breaker curves
Not checked
A circuit that fails a check says so on its board’s list and its page, with MagiCAD’s figures beside what they are checked against.
- Save to
- Any folder, OneDrive and DFS included; a symbolic link or junction in the path is refused
- Formula-like text
- Gets an apostrophe in front, in both CSV and Copy
- Text too long for a cell
- Replaced or cut, never stopping the export