Drop to tray, on the Route panel, gives each device in a list its own conduit drop to an automatically chosen cable tray, or to a tray you pick. Doing this by hand for every outlet takes a large share of modelling time. Drops that can be reached are added together, and devices that can’t are named so you can deal with them.

Each selected device gets its own drop to the nearest cable tray.

Drop devices to a tray

  1. Select the devices

    Select the devices and click Drop to tray. The device list opens with your selection, and you can add or remove devices there. Add devices in view without a route adds visible devices that have no route yet.

  2. Click Suggest drops

    Each device is planned to the nearest trays within reach. There is no fixed limit on how many devices you list.

  3. Review the drops

    The review shows the reachable drops together, the devices that were skipped and why, where each drop meets its tray and any device end that isn’t joined. Show in view finds a device that failed.

  4. Add the drops

    Click Add. When some devices failed, the button reads Add N of M drops and Cancel is the default. After you add, the failed devices stay selected.

Pick the tray yourself

In the review, or after a refusal, Target tray lets you pick a tray in this model or in a loaded link. A picked tray is the only target; other trays stay obstacles. Press Esc to keep the tray you had before.

Which trays it reaches

What Drop to tray works with

  • Straight cable trays in this model

    Supported
  • Straight cable trays in loaded linked models

    Supported
  • Angled, sloped, vertical and rotated-link trays

    Supported. Wider checks in Revit are still open.

    Partial
  • Tray fittings, such as bends and tees, as targets

    Not supported
  • Devices with no free opening

    They are left out of the plan.

    Not supported

A drop comes up through the bottom of the tray or in through a side rail. Coming down into the open top is off by default. Every entry needs room, and can’t be closer to the end of a tray than the conduit radius plus 50 mm.

Settings

SettingDefaultWhere
How far to look for a tray10000 mm (500 to 30000 mm)My settings › Routing, or More › Change drop options for this document
Bottom entryOnMy settings › Routing
Side entryOnMy settings › Routing
Top entryOffMy settings › Routing
Trays each drop tries, nearest first4 (1 to 16)My settings › Performance
Extra memory for a batch512 MiBMy settings › Performance

When a device can’t be reached

A refusal can offer a longer reach, another entry face, more search time or other drop content, for this command only. Devices that still can’t be reached stay selected after Add, ready for another try.

What it doesn’t do

  • It doesn’t run conduit along the tray, and never moves devices or changes trays.
  • It never adds a drop you haven’t reviewed.
  • Memory and search limits still apply. When memory runs low, the batch is rolled back.