Pick a start and an end, and Route A→B finds a conduit route that keeps clear of everything set to Avoid, with real elbows and the straight run each one needs. It is checked against the model’s real geometry and shown for review before anything stays.

Pick a start and an end. Pembris finds a route around what to avoid and shows it for review.

Route between two devices

  1. Click Route A→B

    On the Route panel. If you select the two ends first, the picks are skipped. With three or more devices selected, it offers Connect devices instead.

  2. Pick a start

    A device, or the open end of a conduit or fitting. Esc cancels the pick.

  3. Pick an end

    A small window shows progress while the route is planned, and lets you cancel.

  4. Review the suggestion

    See what it passes through and any end that isn’t joined. See Review a suggested route.

  5. Click Add conduit

    Or press Enter. The route is added as one undo step.

The review shows the route, what it passes through and any unjoined end.

What a route keeps to

RuleDefaultWhere to change it
Avoid or Go throughBeams, walls and ceilings Go through; everything else is avoidedMy settings › Obstacles
Clearance25 mm from every Avoid elementMy settings › Routing
Bend limit360° between pull pointsMy settings › Routing › Bends
Minimum straight runAutomatic, from the elbow sizeMy settings › Routing › Bends
Routing directionPrefer upwardMy settings › Routing, or More › Change layout for one route
Default heightNew settings start on Above the ceiling, or under the slab where there is no ceilingMy settings › Routing
Search time5 sMy settings › Performance › Search harder

What else it handles

  • A route that continues an existing run keeps its conduit type, size and Service Type.
  • A route leaves the building through an exterior wall only when it must, and the review names the run that does.
  • Sockets, switches and lights without conduit connectors can be routed to. The conduit ends at the device, marked Not joined.
  • A device inside another element, such as a socket in its junction box, gets a short straight way out, listed as a permitted penetration.
  • Two to four conduits side by side between two boxes with free openings, set in More › Change layout.