Pembris Electrical adds up the bends in each run between two pull points and keeps them within your bend limit: 360°, the NEC limit, unless you change it. A run over the limit is never called compliant.
What counts as a run
A run is the conduit between two devices, and each device counts as a pull point. Pembris Electrical doesn’t place pull boxes for you.
Settings
All three are in My settings › Routing › Bends.
| Setting | Choices | Default |
|---|---|---|
| Bend limit between pull points | 360° (NEC), 270°, 180°, or Custom from 90° to 720° | 360° (NEC) |
| When a run has too many bends | Warn in the suggestion, Ask before adding, Don’t suggest it, Don’t check bends | Warn in the suggestion |
| Minimum straight run | Automatic, or Custom | Automatic |
When a run has too many bends
Before it warns or refuses, the search tries once more, avoiding bends harder, to find a route within the limit. If there still isn’t one:
| Choice | What happens |
|---|---|
| Warn in the suggestion | The route is offered, and the review warns, naming the run and your limit. |
| Ask before adding | The review asks you to confirm: Cancel is the default and the primary says Add anyway. |
| Don’t suggest it | Only suggestions within the limit are offered. If none is, nothing is drawn, and the refusal offers Show it with a warning this time. |
| Don’t check bends | No limit and no retry. |
Elbows and straight runs
Routes are planned with the real size of your project’s elbows and keep the straight run each elbow needs beside every bend. Minimum straight run on Automatic works it out from the elbow size; Custom sets your own length.
Checking bends later
Check routes and Check project check bends too. A route’s page in Check routes shows a Bends bar: red over the limit, amber within 10% of it, grey otherwise. The bend check can be turned off in My settings › Checks; it also needs the limit not set to Don’t check bends.